Series i/o module tb1 wiring examples (continued) – Rockwell Automation 21G PowerFlex 750-Series AC Drives User Manual

Page 234

Advertising
background image

234

Rockwell Automation Publication 750-IN001N-EN-P - April 2014

PowerFlex 750-Series AC Drives

2-Wire Control Non-
Reversing
24V DC internal supply

11-Series I/O Module TB1

Set Direction Mode

Port 0: P308 [Direction Mode] = 2 “Rev Disable”

Configuration

Port 0: P150 [Digital In Cfg] = 1 “Run Level”

Set Selection

Port 0: P163 [DI Run] = Port X (11-Series I/O Module): P1 [Dig In Sts], bit 0 = Input 0

View Results

Port X (11-Series I/O Module): P1 [Dig In Sts]
Port 0: P935 [Drive Status 1]

2-Wire Control Reversing
External 24 volt supply

20-750-1132C-2R
20-750-1133C-1R2T

11-Series I/O Module TB1

Set Direction Mode

Port 0: P308 [Direction Mode] = 0 “Unipolar”

Configuration

Port 0: P150 [Digital In Cfg] = 1 “Run Level”

Set Selection

Port 0: P164 [DI Run Forward] = Port X (11-Series I/O Module): P1 [Dig In Sts], bit 0 = Input 0
Port 0: P165 [DI Run Reverse] = Port X (11-Series I/O Module): P1 [Dig In Sts], bit 1 = Input 1

View Results

Port X (11-Series I/O Module): P1 [Dig In Sts]
Port 0: P935 [Drive Status 1]

3-Wire Control
Internal supply

11-Series I/O Module TB1

Set Selection

Port 0: P158 [DI Stop] = Port X (11-Series I/O Module): P1 [Dig In Sts], bit 0 = Input 0
Port 0: P161 [DI Start] = Port X (11-Series I/O Module): P1 [Dig In Sts], bit 1 = Input 1

View Results

Port X (11-Series I/O Module): P1 [Dig In Sts]
Port 0: P935 [Drive Status 1]

11-Series I/O Module TB1 Wiring Examples (Continued)

Input/Output

Connection Example

Required Parameter Changes

Di0

Di0P

Stop-Run

P3

P8

3

1

3

1

Di0

Di0P

Di1

Di1P

Ip

Ic

+24V

Common

Run Fwd

Run Rev

P3

P8

3

1

3

1

Di0

Di0P

Di1

Di1P

Stop

Start

P3

P8

3

1

3

1