Rockwell Automation 21G PowerFlex 750-Series AC Drives User Manual

Page 198

Advertising
background image

198

Rockwell Automation Publication 750-IN001N-EN-P - April 2014

PowerFlex 750-Series AC Drives

Wall Mount Frames 1, 6, and 7 Power Jumper Wire Removal and
Storage

Wall/Flange Mount Frames 1, 6, and 7 use jumper wires to complete an electrical
connection when installed. Install or remove jumper wires according to the
recommendations in

Table 29

.

Figure 107 - Wall Mount Frame 1 Jumper Wire Locations

When jumper wires are connected, the spade connector should be pressed firmly
onto the sheet metal tab.

ATTENTION: Hazard of equipment damage exists if jumpers are not properly
disconnected. For Frames 1, 6, and 7, secure the disconnected jumper wire to the
insulated position provided.

PE-A

PE-B

Disconnected

Connected

Disconnected

Connected

Advertising