Rockwell Automation Publication 750-IN001N-EN-P - April 2014

PowerFlex 750-Series AC Drives

Port Assignment

When used in an Integrated Motion application, the Safe Torque Off
option must be installed in port 6.

Only one safety option module can be installed at a time. Multiple safety
options or duplicate safety option installations are not supported.

Jumper Settings

Ensure the hardware enable jumper (ENABLE) on the main control board
is installed. Refer to

page 214

for location. If not installed, the drive will

fault when powered up.

Ensure the safety enable jumper (SAFETY) on the main control board is
removed (Frames 1…7 only). Refer to

page 216

for location.