Rockwell Automation 21G PowerFlex 750-Series AC Drives User Manual

Page 276

Advertising
background image

276

Rockwell Automation Publication 750-IN001N-EN-P - April 2014

PowerFlex 750-Series AC Drives

Control Wiring - Early Frame 8 Drives with Cabinet Options

Control terminal block TB2 is mounted on the inside right panel of the cabinet options bay
on early production frame 8 drives. TB1 referenced in the illustrations below resides on the
main control board. See

page 213

.

Table 97 - TB2 Terminal Block Specifications

Figure 140 - Control Terminal Block TB2 - Floor Mount Frame 8 Drives

Table 98 - Input/Output Contactor Data

Name

Wire Size Range

Torque

Strip
Length

Maximum

Minimum

Maximum

Recommended

Control Terminal Block TB2

4.0 mm

2

(12 AWG)

0.5 mm

2

(20 AWG)

0.5 N•m
(4.5 lb•in)

0.4 N•m
(3.5 lb•in)

8 mm
(0.32 in.)

6

7

8

9

10

6

7

8

9

10

1

2

3

4

5

1

2

3

4

5

Input/Output Contactor

M2/M4

TB2(8)

TS1

Thermostat

TB2

W1

Hardware Enable Jumper

Note: Remove W1 jumper to

connect a hardware enable circuit.

TB2(7)

TB2(6)

TB1(Di 0dc)

TB2(1)

TB1(+24V)

A1

A2

13

14

TB2(9)

TB2(4)

M2/M4

21

22

TB2(5)

TB2(10)

M2/M4

TB2(3)

Optional Devices

Cat. No.

(1)

(1) For full contactor specifications refer to publications 100D-SG001 and 100G-SG001.

Input

Pick-Up

Hold-In

100-D420EA11

50 Hz

490VA

18VA

100-D420ED11

60 Hz

490VA

18VA

100-D630EA11

50 Hz

1915VA

33VA

100-D630ED11

60 Hz

1915VA

33VA

100-D860EA11

50 Hz

1915VA

33VA

100-D860ED11

60 Hz

1915VA

33VA

100-G1200KD12

60 Hz

2,400VA

70VA

Advertising