Rockwell Automation Publication 750-IN001N-EN-P - April 2014

255

PowerFlex 750-Series AC Drives

20-COMM Carrier

Enables use of some 20-COMM adapters with PowerFlex 750-Series drives. See

Table 84

.

Refer to publication

750COM-IN001

for instructions on installing a 20-

COMM adapter on the 20-COMM Carrier.

Table 84 - 20-COMM-* Network Adapter Compatibility with 750-Series Drives

Frame 1 Drives Installation Recommendations

PowerFlex Frame 1 drives require the use of the 20-750-20COMM-F1
Communication Carrier kit. This kit contains the required adapter plate.

Only install the 20-750-20COMM-F1 Communication Carrier in Port 4.
See

page 228

for port locations. Port 5 will not be accessible when this

module is installed.

Frame 2 and Larger Drives Installation Recommendations

Installing the 20-750-20COMM Communication Carrier in Port 6 is
recommended. Installing in Port 4 or Port 5 will make the adjacent left
port inaccessible to other option modules, and may interfere with network
cable connections.

20-750-20COMM-F1

20-750-20COMM

Frame 1

Frames 2 and Larger

Adapter

Accesses Ports 0…6

for I/O Connections

(Implicit and Explicit Messaging)

Accesses Ports 7 and

Higher

(I/O, Explicit

Messaging)

Supports Drive Add-on

Profiles

Supports Asian-

Languages

(6)

(6) Chinese, Japanese, and Korean languages are supported at the time of publication.

Cat. No.

Type

20-COMM-B

BACnet MS/TP

Not Compatible

20-COMM-C

ControlNet

(Coax)

✓ v3.001

(4)

✓ v3.001

(4)

(4) Requires this adapter firmware version or higher.

(5)

(5) Requires firmware version v1.05 or higher of the drive Add-on Profiles for RSLogix 5000 version v16 or higher.

✓ v3.001

(4)

20-COMM-D

DeviceNet

(2)

(2) Controller must be capable of reading/writing 32-bit floating point (REAL) values.

Not Compatible

20-COMM-E

EtherNet/IP

✓ v4.001

(4)

✓ v4.001

(4)

(5)

✓ v4.001

(4)

20-COMM-H

RS-485 HVAC

✓ v2.009

(3) (4)

(3) Supports all three modes of operation (RTU, P1, N2).

Not Compatible

20-COMM-K

CANopen

✓ v1.001

(4)

20-COMM-L

LonWorks

✓ v1.007

(4)

20-COMM-M

Modbus/TCP

✓ v2.001

(4)

✓ v2.001

(4)

Not Compatible

✓ v2.001

(4)

20-COMM-P

ControlNet

(Fiber)

✓ v1.006

(4)

✓ v1.006

(4)

Not Compatible

20-COMM-Q

PROFIBUS DP

✓ v3.001

(4)

✓ v3.001

(4)

(5)

✓ v3.001

(4)

20-COMM-R

(1)

(1) This item has

Silver Series

status.

Remote I/O

(2)

Not Compatible

20-COMM-S

RS-485 DF1