Table 1 – Rockwell Automation 21G PowerFlex 750-Series AC Drives User Manual

Page 17

Advertising
background image

Rockwell Automation Publication 750-IN001N-EN-P - April 2014

17

PowerFlex 750-Series AC Drives

Table 1 - PowerFlex 750-Series 400/480V Input Drives RF Emission Compliance and Installation
Requirements

Standard / Limits

Drive Frame
Catalog Number

EN61800-3 Category C1
EN61000-6-3
CISPR11 Group 1 Class B

EN61800-3 Category C2
EN61000-6-4
CISPR11 Group 1 Class A
(Input power

20 kVA)

EN61800-3 Category C3
(I

100 A)

CISPR11 Group 1 Class A
(Input power > 20 kVA)

EN61800-3 Category C3
I > 100 A

Wall Mount Frame 1
20F11xx2P1…20F11xx015
20G11xx2P1…20G11xx015

N/A

30 m motor cable limit with each wire
looped once around an input core.

(1)

(2)

30 m motor cable limit with each wire
looped once around an input core.

(1)

N/A

Wall Mount Frame 2
20F11xx2P1…20F11xx022
20G11xx2P1…20G11xx022

150 m cable limit with Schaffner
FN3258-30-nn filter.
Supplementary EMC enclosure
required to provide attenuation of
radiated emissions.

30 m motor cable limit with input core.

(1)

150 m motor cable limit with Schaffner
FN3258-30-nn filter.

30 m motor cable limit with input core.

(1)

150 m motor cable limit with Schaffner
FN3258-30-nn filter.

N/A

Wall Mount Frame 3
20F11xx030…20F11xx043
20G11xx030…20G11xx043

150 m cable limit with Schaffner
FN3258-55-nn filter.
Supplementary EMC enclosure
required to provide attenuation of
radiated emissions.

30 m motor cable limit with input core.

(1)

150 m motor cable limit with Schaffner
FN3258-55-nn filter.

30 m motor cable limit with input core.

(1)

150 m motor cable limit with Schaffner
FN3258-55-nn filter.

N/A

Wall Mount Frame 4
20F11xx060…20F11xx072
20G11xx060…20G11xx072

150 m cable limit with Schaffner
FN3258-75-nn filter.
Supplementary EMC enclosure
required to provide attenuation of
radiated emissions.

30 m motor cable limit with input and
output cores.

(1)

150 m motor cable limit with Schaffner
FN3258-75-nn filter.

30 m motor cable limit with input and
output cores.

(1)

150 m motor cable limit with Schaffner
FN3258-75-nn filter.

N/A

Wall Mount Frame 5
20F11xx085…20F11xx104
20G11xx085…20G11xx104

150 m cable limit with Schaffner
FN3258-130-nn filter.
Supplementary EMC enclosure
required to provide attenuation of
radiated emissions.

30 m motor cable limit with input and
output cores.

(1)

150 m motor cable limit with Schaffner
FN3258-130-nn filter.

30 m motor cable limit with input and
output cores.

(1)

150 m motor cable limit with Schaffner
FN3258-130-nn filter.

30 m motor cable limit with input and
output cores.

(1)

150 m motor cable limit with Schaffner
FN3258-130-nn filter.

Wall Mount Frame 6
20F11xx140…20F11xx260
20G11xx140…20G11xx260

150 m cable limit with 22-RFD323
filter.
Supplementary EMC enclosure
required to provide attenuation of
radiated emissions.

100 m motor cable limit with Schaffner
FN3359-320-nn filter.
150 m motor cable limit with 22-RFD323
filter.
Supplementary EMC enclosure required to
provide attenuation of radiated emissions.

30 m motor cable limit with no filter.

(3)

100 m motor cable limit with Schaffner
FN3359-320-nn filter.
150 m motor cable limit with 22-RFD323
filter.

30 m motor cable limit with no filter.

(3)

100 m motor cable limit with Schaffner
FN3359-320-nn filter.
150 m motor cable limit with 22-RFD323
filter.

Wall Mount Frame 7
20F11xx302…20F11xx456
20G11xx302…20G11xx456

150 m cable limit with 22-RFD480
filter.
Supplementary EMC enclosure
required to provide attenuation of
radiated emissions.

150 m motor cable limit with Schaffner
FN3359-600-nn filter.
150 m motor cable limit with 22-RFD480
filter.
Supplementary EMC enclosure required to
provide attenuation of radiated emissions.

30 m motor cable limit with no filter.

(3)

150 m motor cable limit with Schaffner
FN3359-600-nn filter.
150 m motor cable limit with 22-RFD480
filter.

30 m motor cable limit with no filter.

(3)

150 m motor cable limit with Schaffner
FN3359-600-nn filter.
150 m motor cable limit with 22-RFD480
filter.

Floor Mount Frame 8 - AC Input
20G1Axx460…20G1Axx770
21G1Axx460…21G1Axx770

Compliance possible with
supplementary mitigation
(Consult factory)

Compliance possible with supplementary
mitigation
(Consult factory)

30 m motor cable limit

(3)

with output

core.

(4)

30 m motor cable limit

(3)

with output

core.

(4)

Floor Mount Frame 9 - AC Input
20G11xx910…20G11xx1K5
21G11xx910…21G11xx1K5

Compliance possible with
supplementary mitigation
(Consult factory)

Compliance possible with supplementary
mitigation
(Consult factory)

30 m motor cable limit

(3)

with output

core

(4)

and input core.

30 m motor cable limit

(3)

with output

core

(4)

and input core.

Floor Mount Frame 10 - AC Input
20G11xx1K6…20G11xx2K1
21G11xx1K6…21G11xx2K1

Compliance possible with
supplementary mitigation
(Consult factory)

Compliance possible with supplementary
mitigation
(Consult factory)

30 m motor cable limit

(3)

with output

core

(4)

and input core. Door shielding kit

installed.

(5)

30 m motor cable limit

(3)

with output

core

(4)

and input core. Door shielding kit

installed.

(5)

Floor Mount Frames 8…9 -
Common DC Input
20G14xx460…20G14xx1K5
21G14xx460…21G14xx1K5

Compliance possible with
supplementary mitigation
(Consult factory)

Compliance possible with supplementary
mitigation
(Consult factory)

30 m motor cable limit

(3)

with output

core

(4)

and input core.

(6)

30 m motor cable limit

(3)

with output

core

(4)

and input core.

(6)

Floor Mount Frame 10 - Common
DC Input
20G14xx1K6…20G14xx2K1
21G14xx1K6…21G14xx2K1

Compliance possible with
supplementary mitigation
(Consult factory)

Compliance possible with supplementary
mitigation
(Consult factory)

30 m motor cable limit

(3)

with output

core

(4)

and input core.

(6)

Door shielding

kit installed.

(5)

30 m motor cable limit

(3)

with output

core

(4)

and input core. Door shielding kit

installed.

(5)

More Stringent Limits

Less Stringent Limits

(1) Rating-specific EMC cores are part of EMC kit numbers 20-750-EMC1-nn and 20-750-EMC2-nn.
(2) To meet the C2 rating with a Dual Encoder module installed, Frame 1 drives must be installed in a supplementary EMC enclosure to attenuate radiated emissions.
(3) Intended to be powered from an industrial power network supplied by a dedicated power transformer or generator and not from LV power lines supplying other customers.
(4) EMC kit number 20-750-EMCCM1-F8. Kit contains one core. Each drive assembly requires one EMC kit. Order one kit for a Frame 8 drive, two kits for a Frame 9 drive, three kits for a Frame 10 drive.
(5) Door shielding kit number 20-750-EMCDK1-F10. Kit contains shielding brackets for three doors.
(6) EMC kit number 20-750-CBPEMCCM1-F8. Kit contains one core. Each drive assembly requires one EMC kit. Order one kit for a Frame 8 drive, two kits for a Frame 9 drive, three kits for a Frame 10 drive.

Advertising