Control Pod Cable Routing

Floor Mount Frames 8…10

Supports, clips, and cable ties are provided to help route cabling inside the control pod.

Figure 139 - Control POD Detail

IMPORTANT

When routing cabling into the control POD, do not block the cooling fan outlet.

Do not ground shield wires to inner sheet metal bucket supporting option
modules.

No. Description

I/O Signal shield termination points. Use M4 screws and ring terminals provided to tie together and terminate
drain wires and shields.

Ground shield wires to outer sheet metal bucket. Strip cable insulation 25 mm (1 in.) to expose braid. Attach cable
ties around shield and through slots. Pull tight.

Attachment points for cable management devices provided (6 places).

Cable support ladder.

Fan outlet. Keep clear to help ensure proper cooling.

Control cable entry and routing.

Human Interface Module (HIM) cable entry and routing.

Shield termination points.