Rockwell Automation Publication 750-IN001N-EN-P - April 2014

233

PowerFlex 750-Series AC Drives

Analog Voltage Input
Unipolar Speed Reference
0 to +10V Input

11-Series I/O Module TB1

Set Direction Mode

Port 0: P308 [Direction Mode] = 0 “Unipolar”

Set Selection

Port 0: P545 [Spd Ref A Sel] = Port X (11-Series I/O Module): P50 [Anlg In0 Value]

Adjust Scaling

Port X (11-Series I/O Module): P51 [Anlg In1 Hi] = 10 Volt
Port X (11-Series I/O Module): P52 [Anlg In1 Lo] = 0 Volt
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz

View Results

Port X (11-Series I/O Module): P50 [Anlg In0 Value]
Port 0: P592 [Selected Spd Ref]

Analog Current Input
Unipolar Speed Reference
0-20 mA Input

11-Series I/O Module TB1

Set Direction Mode

Port 0: P308 [Direction Mode] = 0 “Unipolar”

Set Selection

Port 0: P545 [Spd Ref A Sel] = Port X (11-Series I/O Module): P50 [Anlg In0 Value]

Adjust Scaling

Port X (11-Series I/O Module): P51 [Anlg In0 Hi] = 20 mA
Port X (11-Series I/O Module): P52 [Anlg In0 Lo] = 0 mA or 4 mA
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz

View Results

Port X (11-Series I/O Module): P50 [Anlg In0 Value]
Port 0: P592 [Selected Spd Ref]

Analog Voltage Output
±10V, 0…20 mA Bipolar
+10V Unipolar

11-Series I/O Module TB1

Configuration

Port X (11-Series I/O Module): P70 [Anlg Out Type], bit 0 = 0

Set Selection

Port X (11-Series I/O Module): P75 [Anlg Out0 Sel] = Port 0: P3 [Mtr Vel Fdbk]

Adjust Scaling

Port X (11-Series I/O Module): P78 [Anlg Out0 DataHi] = 60 Hz
Port X (11-Series I/O Module): P79 [Anlg Out0 DataLo] = 0 Hz
Port X (11-Series I/O Module): P80 [Anlg Out0 Hi] =10V/20 mA
Port X (11-Series I/O Module): P81 [Anlg Out0 Lo] = 0V/0 mA

View Results

Port X (11-Series I/O Module): P77 [Anlg Out0 Data]
Port X (11-Series I/O Module): P82 [Anlg Out0 Val]

11-Series I/O Module TB1 Wiring Examples (Continued)

Input/Output

Connection Example

Required Parameter Changes

Ai0–

Ai0+

Sh

Common

+

P5

1

2

P4

1

2

Ai0–

Ai0+

Sh

Common

+

P5

1

2

P4

1

2

Ao0–

Ao0+

Sh

+