3-38

TCP/IP Ethernet Communications for the Series 90™ PLC User's Manual

May 2002

GFK-1541B

3

Minor Error Codes

The meaning of each Minor Error Code depends upon the Major Error Code for which it is
defined. Consult the appropriate Minor Error Code table for the indicated Major Error Code.

Minor Error Codes for Major Error Codes 05H (at Remote Server PLC) and

85H (at Client PLC)

Error Status

Service Request Error Description

(Hexadecimal)

C105H/C185H

Invalid block state transition.

C305H/C385H

Text length does not match traffic type.

C605H/C685H

Control Program (CP) tasks exist but requestor not logged into main CP.

C705H/C785H

Passwords are set to inactive and cannot be enabled or disabled.

C805H/C885H

Password(s) already enabled and cannot be forced inactive.

C905H/C985H

Login using non-zero buffer size required for block commands.

CA05H/CA85H Device is write-protected.

CB05H/CB85H

A comm or write verify error occurred during save or restore.

CC05H/CC85H

Data stored on device has been corrupted and is no longer reliable.

CD05H/CD85H Attempt was made to read a device but no data has been stored on it.

CE05H/CE85H

Specified device has insufficient memory to handle request.

CF05H/CF85H

Specified device is not available in the system (not present).

D105H/D185H

Packet size or total program size does not match input.

D205H/D285H

Invalid write mode parameter.

D505H/D585H

Invalid block name specified in datagram.

D605H/D685H

Total datagram connection memory exceeded.

D705H/D785H

Invalid datagram type specified.

D805H/D885H

Point length not allowed.

D905H/D985H

Transfer type invalid for this Memory Type selector.

DA05H/DA85H Null pointer to data in Memory Type selector.

DB05H/DB85H Invalid Memory Type selector in datagram.
DC05H/DC85H Unable to find connection address.

DD05H/DD85H Unable to locate given datagram connection ID.

DE05H/DE85H

Size of datagram connection invalid.

DF05H/DF85H

Invalid datagram connection address.

E005H/E085H

Service in process cannot login.

E405H/E485H

Memory Type for this selector does not exist.

E905H/E985H

Memory Type selector not valid in context.

EA05H/EA85H

Not logged in to process service request.

EE05H/EE85H

Could not return block sizes.

EF05H/EF85H

Programmer is already attached.

F005H/F085H

Request only valid in stop mode.

F105H/F185H

Request only valid from programmer.

F205H/F285H

Invalid program cannot log in.

F405H/F485H

Invalid input parameter in request.

F505H/F585H

Invalid password.

F605H/F685H

Invalid sweep state to set.

www.cadfamily.com EMail:[email protected]
The document is for study only,if tort to your rights,please inform us,we will delete

Advertising