Chapter 2 Installation

2-21

2

Installing the CPU364 in the PLC

For general information about module and system installation, refer to GFK-0356, Series 90-30
Programmable Controller Installation Manual

.

Equipment Required to Perform the Installation Procedures

Make sure you have the items listed below before you begin.

ƒ

A Series 90-30 PLC CPU baseplate with power supply. The Series 90-30 CPU364 requires
PLC power supply IC693PWR321 (Revision K or later), IC693PWR322, or IC693PWR330.

ƒ

PLC programming software: Logic Developer (all versions), Control Version 2.01 or higher,
VersaPro

 version 1.0 or higher, or Logicmaster 90-30 version 6.01 or higher. (And a

compatible PC-compatible personal computer.)

ƒ

Ethernet cables and, if using the AAUI port, an Ethernet-compatible AAUI transceiver. (See
Appendix B, “Communications Port Characteristics”, for more information.)

ƒ

A serial cable for the Station Manager port on the Ethernet Interface (see Appendix B).
Optional

ƒ

A terminal or IBM-compatible personal computer equipped with terminal emulation
software. Optional

Note: If your installation requires CE Mark compliance, please refer to GFK-1179,
Installation Requirements for Conformance to Standards

, for additional guidelines.

CPU364 Installation

Use the following instructions as a guide when inserting a module into a slot in a baseplate.
These instructions assume that the power supply on the baseplate is to your left.

Warning

Do not insert or remove modules with power applied. This could cause the
PLC to Stop, damage the module, or result in personal injury.

1

.

Be sure the Series 90-30 PLC baseplate power is OFF.

2

.

Align the module with the CPU’s base slot (slot 1) and connector. Tilt the module upwards
so that the top rear hook of the module engages the slot on baseplate.

3

.

Swing the module downward until the connectors mate and the lock-lever on the bottom of
the module snaps into place engaging the baseplate notch.

4

.

Visually inspect the module to be sure that it is properly seated.

5

.

Connect one of the Ethernet ports on the Ethernet Interface to the network. If you are using
an external transceiver, connect the transceiver cable to the 14-pin AAUI port of the Ethernet
Interface. Secure the cable. The other end of the transceiver cable should be connected to an
external IEEE 802.3 compatible transceiver which is attached to the Ethernet network. SQE
must be enabled on the transceiver.
(Note: The transceiver cable may be built-in to the
transceiver or removable.)

Caution

Do not connect or disconnect a transceiver cable to the AAUI port while
power is applied to the PLC. This may blow the AAUI port fuse and/or
cause permanent damage to the Ethernet Interface.

6

.

Restore power to the baseplate.

7

.

Use the PLC programming software or a Hand Held Programmer to make sure the PLC CPU
is in Stop mode.