Chapter 2 Installation

2-53

2

LED Pattern

Where Stopped

Possible Cause

Corrective Actions

MODULE OK OFF)

LAN ONLINE (OFF)

SERIAL ACTIVE (OFF)

STATUS (OFF)

A

Hardware

Failure

Fatal Hardware Error.

ƒ

Make sure the PLC has power.

ƒ

Examine PLC Fault Table for
clues.*

ƒ

Recheck PLC Programmer
configuration.

ƒ

Power off the PLC rack, inspect the
Interface for loose components,
reseat the Interface, and Restart.

ƒ

Try a different slot.

ƒ

If the problem persists, replace the
Interface or PLC hardware.

MODULE OK (Slowblink)

LAN ONLINE (Slowblink)

SERIAL ACT. (Slowblink)

STATUS (Slowblink)

All LEDs blink in unison.

B

Software

Loader

ƒ

Restart pushbutton until the
bottom LED turns ON.

ƒ

Station Manager LOAD
command issued.

ƒ

Software corrupt.

ƒ

Connect a PC Software Loader and
load new software. See Appendix C.

ƒ

Cycle power or press Restart
pushbutton again for less than 5
seconds to restart the Interface and
clear the load request.

MODULE OK (Slowblink)

LAN ONLINE (OFF)

SERIAL ACT. (OFF)

Status (OFF)

C

Waiting for

Configuration

from PLC

ƒ

Did not configure slot using
PLC Programmer.

ƒ

New CPU with no
configuration.

ƒ

CPU not communicating
with Ethernet Interface

ƒ

(Condition can last a
maximum of 2 minutes.)

ƒ

Use configuration software to
configure the Interface then store
the configuration to the PLC CPU.

ƒ

Make sure Interface is in the correct
slot on the in the PLC rack.

ƒ

Power cycle the PLC.

ƒ

Clear faults and Restart Interface.

MODULE OK (Slowblink)

/

✲/

LAN ONL. (ON/Traffic/OFF)

SER. ACT (OFF/Slowblink)

STAT US (Slowblink)

MODULE OK and STATUS blink in
unison.

D

Waiting for IP

Address

Interface’s IP address has not
been configured or has been
configured as 0.0.0.0.

ƒ

Use PLC Programmer configuration
software to configure the Interface
with a non-zero IP address.

ƒ

Use a BOOTP server to provide
Interface with a non-zero IP
Address.

MODULE OK (Slowblink)

/

✲/

LAN ONL. (ON/Traffic/OFF)

SERIAL ACT. (Slowblink)

/

STATUS (ON/OFF)

MODULE OK and SERIAL ACTIVE
blink in unison.

E

Maintenance

ƒ

Restart pushbutton until
bottom two LEDs turn ON.

ƒ

Station Manager MAINT
command issued.

ƒ

Internal System Error when
Interface was Operational
caused a restart and
entrance into Maintenance.

ƒ

If you did not intend to enter
Maintenance, press the Restart
pushbutton for less than 5 seconds.
This clears the Maintenance request.

ƒ

Examine PLC Fault Table for
clues.*

ƒ

If you need to use the Station
Manager to troubleshoot a problem,
see GFK-1186, TCP/IP Ethernet
Communications for the Series 90
PLC Station Manager Manual.

MODULE OK

(ON)

/

✲/

LAN ONL. (ON/Traffic/OFF)

SERIAL ACTIVE (OFF)

/

STATUS (ON/OFF)

F

Operational

If the LAN ONLINE LED is
OFF, the problem may be:
ƒ

Network cable not
connected or transceiver not
connected to Interface or
bad transceiver.

ƒ

Network cable not
terminated properly.

ƒ

SQE not enabled on
transceiver.

If the STATUS LED is OFF, an
exception condition has
occurred.

ƒ
ƒ

Connect cable and transceiver
properly. Replace transceiver.

ƒ

Terminate network cable properly.

ƒ

Set SQE ON on transceiver in
accord with manufacturer’s
instructions.

ƒ

Examine PLC Fault Table to find
out why the STATUS LED is OFF.
*