The commreq command block – FANUC Robotics America GFK-1541B User Manual

Page 74

Advertising
background image

GFK-1541B

Chapter 3 Programming Channel Commands

3-7

3

TASK:

For the Series 90-30 CPU364, this must always be set to 21 decimal (0015H). For the

Series 90-30 Ethernet Interface and the Series 90-70 Ethernet Interface (Type2), this must always
be set to zero.

Caution

Entering an incorrect TASK value may cause the Ethernet Interface to fail.

OK Output:

(Series 90-70 PLC only) The OK output is set if the PLC CPU has successfully

delivered the COMMREQ to the Ethernet Interface.

FT Output:

The FT output is set if the PLC CPU (rather than the Ethernet Interface) detects that

the COMMREQ fails. In this case, the other status indicators are not updated for this
COMMREQ.

The COMMREQ Command Block

When the COMMREQ function is initiated, the Command Block is sent from the PLC CPU to the
Ethernet Interface. The Command Block contains the details of a Channel command to be
performed by the Interface.

The address in CPU memory of the Command Block is specified by the IN input of the
COMMREQ Function Block. This address can be any valid address within a word-oriented area
of memory (%R, %AI, or %AQ for the Series 90-30 Ethernet Interface and the Series 90-30
CPU364) (%R, %AI, %AQ, %P, or %L for the Series 90-70 Ethernet Interface (Type 2)). The
Command Block is set up using an appropriate programming instruction (the BLOCK MOVE or
DATA_INIT (Series 90-70 PLC only) Function Blocks are recommended).

The Command Block has the following structure:

Word 1

Data Block Length (words)

Word 2

WAIT/NOWAIT Flag

Word 3

CRS Word Memory Type

Word 4

CRS Word Address Offset

Word 5

Reserved

Word 6

Reserved

Words 7 and up

Data Block (Channel Command Details)

When entering information for the Command Block, refer to these definitions:

(Word 1) Data Block Length:

This is the length in words of the Data Block portion of the

Command Block. The Data Block portion starts at Word 7 of the Command Block. The length is
measured from the beginning of the Data Block at Word 7, not from the beginning of the
Command Block. The correct value for each command, and the associated length of each
command, is specified in the next section.

(Word 2) WAIT/NOWAIT Flag:

This flag must be set to zero for TCP/IP Ethernet

Communications.

www.cadfamily.com EMail:[email protected]
The document is for study only,if tort to your rights,please inform us,we will delete

Advertising