3-40

TCP/IP Ethernet Communications for the Series 90™ PLC User's Manual

May 2002

GFK-1541B

3

Minor Error Codes for Major Error Code 11H (at Remote Server PLC) -

Continued

2E11H

The maximum number of transfers of this transfer type is already taking place.

2F11H

Cannot obtain a backplane transfer buffer.

3011H

Cannot obtain resources other than backplane transfer buffers.

3111H

Connection ID or block transfer ID is not valid.

3211H

Timed out waiting for PLC CPU response.

3311H

The PLC CPU aborted the request.

3411H

An invalid message type was specified.

3511H

The specified task is not registered.

3611H

The mailbox offset specified is invalid.

3711H

The backplane task could not be registered because the message response handler
was not specified.

3811H

The backplane task could not be registered because the unsolicited mailbox
message handler was not specified.

3911H

The backplane task could not be registered because a required parameter was not
specified.

3A11H

More than the allowable byte length in a single transfer.

3B11H

Bad sequence number in the request.

3C11H

Invalid command in request.

3D11H

Response length does not match length specified in the response qualifier.

3E11H

Request failed because the PLC’s Service Request Processor is not initialized.

3F11H

Request failed due to an error in the remote device, most likely running out of
Dual-Port RAM text buffers.

4011H

Unable to free dual port memory that was allocated for a connection or block
transfer area.

4111H

The backplane task could not be registered because the service request handler was
not specified.

4211H

No dual port memory was allocated for the connection or block transfer area
needed to process the request.

4311H

Failure to register with backplane driver because the requested task is already
registered.

4411H

Request failed because an invalid field was identified in the request mailbox
qualifier.

E811H

Unable to send request to the PLC because an internal message queue is full.

E911H

Unable to send request to the PLC because the text buffer type is invalid.

EA11H

Unable to send request to the PLC because the mailbox utility function is invalid.

EB11H

Unable to send request to the PLC because the mailbox message is not specified.

EC11H

Unable to send request to the PLC because the internal message queue is not
initialized.

FE11H

Request failed due to mailbox error on remote device. The remote device log will
have more information.

Error codes specific to Series 90-30 CPU374*

2911H

The backplane driver is not initialized.

2A11H

The backplane driver could not access the PLC.

2F11H

Request failed due to an invalid parameter detected in the remote device. The
remote device log will have more information.

3011H

The specified task is not registered.