TCP/IP Ethernet Communications for the Series 90™ PLC User's Manual

May 2002

GFK-1541B

2

Installing the CMM321 in the PLC

For general information about module and system installation, refer to GFK-0356, Series 90-30
Programmable Controller Installation Manual

.

Equipment Required to Perform the Installation Procedures

Make sure you have the items listed below before you begin.

ƒ

A Series 90-30 PLC CPU baseplate, or any Series 90-30 baseplate and a Series 90-30 CPU
with power supply.

ƒ

The CMM321 requires CPU version 6.50 or higher for full functionality. CPU versions
5.03 to 6.04 permit Ethernet operation with only 1 SRTP server connection.

ƒ

The CMM321 requires PLC power supply IC693PWR321 (Revision K or later),
IC693PWR322, or IC693PWR330.

ƒ

PLC programming software: Logic Developer (all versions), Control Version 2.01 or higher,
VersaPro

 version 1.0 or higher, or Logicmaster 90-30 version 6.01 or higher. (And a

compatible PC-compatible personal computer.)

ƒ

If you are using the AAUI port instead of the 10Base-T port, you will need an Ethernet-
compatible AAUI transceiver and Ethernet cables. (See Appendix B for more information on
the ports and transceivers.) Optional

ƒ

An

IC693CBL316

serial cable for the Station Manager port on the Ethernet Interface (see

Appendix B). Optional

ƒ

A terminal or IBM-compatible personal computer equipped with terminal emulation
software. Optional

Notes

If your installation requires CE Mark compliance, please refer to GFK-1179,
Installation Requirements for Conformance to Standards

, shipped with the PLC

programming software, for additional guidelines.

A CMM321 can be mounted on a CPU baseplate, an expansion baseplate, or a
remote baseplate. However, due to power requirements, only two Ethernet
Interface modules are permitted per baseplate using a standard power supply.
Up to four Ethernet Interface modules are permitted per baseplate using a high
capacity power supply.

www.cadfamily.com EMail:[email protected]