3-26

TCP/IP Ethernet Communications for the Series 90™ PLC User's Manual

May 2002

GFK-1541B

3

Example 2 Command Block–Example using a Network Address name

This example is the same as Example 1 except that the Network Address name of the remote host
(“PLC_1aa”) is used instead of its IP address. For more information on Network Address names,
see the chapter: “Network Administration Support”.

Establish a channel (Channel 7) to a remote host application server with a Network Address name
of “PLC_1aa”. Return the COMMREQ Status word to %R10. Send local PLC registers
%R50–%R57 to remote host. Repeat the send 10 times, once every 7 seconds, with a timeout of
500 ms for each transfer.

Dec (Hex)

Word 1

00045 (002D)

Length of Send Information Report Data Block (45 words)

Word 2

00000 (0000)

Always 0 (no-wait mode request)

Word 3

00008 (0008)

Memory type of CRS word (%R)

Word 4

00009 (0009)

CRS word address minus 1 (%R10)*

Word 5

00000 (0000)

Reserved

Word 6

00000 (0000)

Reserved

Word 7

02010 (07DA)

Send Information Report Channel command number

Word 8

00007 (0007)

Channel number (7)

Word 9

00010 (000A)

Number of repetitions (send 10 times)

Word 10

00003 (0003)

Time units for send period (3=seconds)

Word 11

00007 (0007)

Minimum interval between host accesses (every 7 seconds)

Word 12

00050 (0032)

Timeout on each individual transfer response (500 ms)

Word 13

00008 (0008)

Local PLC - Memory type from which to send data (%R)

Word 14

00050 (0032)

Local PLC - Starting address from which to send data (%R50)

Word 15

00008 (0008)

Local PLC - Number of memory units (8 registers)

Word 16

00000 (0000)

Reserved

Word 17

00000 (0000)

Reserved

Word 18

00003 (0003)

Remote Host - Network Address type (3=Symbolic Name)

Word 19

00032 (0020)

Remote Host - Network Address length in words (32)

Word 20

19536 (4C50)

Remote Host - Network Address name, char 1–2 (PL)

Word 21

24387 (5F43)

Remote Host - Network Address name, char 3–4 (C_)

Word 22

24881 (6131)

Remote Host - Network Address name, char 5–6 (1a)

Word 23

00097 (0061)

Remote Host - Network Address name, char 7–8 (a )

Word 24

00000 (0000)

Remote Host - Network Address name, char 9–10

Word 25

00000 (0000)

Remote Host - Network Address name, char 11–12

Word 26

00000 (0000)

Remote Host - Network Address name, char 13–14

Word 27

00000 (0000)

Remote Host - Network Address name, char 15–16

Word 28

00000 (0000)

Remote Host - Network Address name, char 17–18

Word 29

00000 (0000)

Remote Host - Network Address name, char 19–20

Word 30

00000 (0000)

Remote Host - Network Address name, char 21–22

Word 31

00000 (0000)

Remote Host - Network Address name, char 23–23

Word 32

00000 (0000)

Remote Host - Network Address name, char 24–25

Word 33

00000 (0000)

Remote Host - Network Address name, char 26–27

Word 34

00000 (0000)

Remote Host - Network Address name, char 28–29

Word 35

00000 (0000)

Remote Host - Network Address name, char 30–31

Word 36–51

Reserved: set to zero

* Word 4 (CRS word address) is the only zero-based address in the Command Block. Only this

value requires subtracting 1 from the intended address.

The term local PLC is
used here to identify the
client PLC—the PLC
that initiates the
communications
request.

The term SRTP Server
is used here to identify
the Host server.