TCP/IP Ethernet Communications for the Series 90™ PLC User's Manual

May 2002

GFK-1541B

2

LED Pattern

Where Stopped

Possible Cause

Corrective Actions

❍ OK (OFF)

❍ LAN (OFF)

❍ FDX (OFF)

❍ STAT (OFF)

A

Hardware

Failure

Fatal Hardware Error.

ƒ

Make sure the PLC has power.

ƒ

Examine PLC Fault Table for clues.*

ƒ

Recheck PLC Programmer
configuration.

ƒ

Power off baseplate, inspect the
Interface for loose components,
reseat the Interface, and Restart.

ƒ

Try a different slot.

ƒ

If the problem persists, replace the
Interface or PLC hardware.

✫ OK (Slowblink)

✫ LAN (Slowblink)

✫ FDX (Slowblink)

✫ STAT (Slowblink)

All LEDs blink in unison.

B

Software

Loader

ƒ

Restart pushbutton until
bottom LED turns ON.

ƒ

Station Manager LOAD
command issued.

ƒ

Software corrupt.

ƒ

Connect a PC Software Loader and
load new software. See Appendix C.

ƒ

Cycle power or press Restart
pushbutton again for less than 5
seconds to restart the Interface and
clear the load request.

✫ OK (Slowblink)

❍ LAN (OFF)

❍ FDX (OFF)

❍ STAT (OFF)

C

Waiting for

Configuration

from PLC

ƒ

Did not configure slot using
PLC Programmer.

ƒ

New CPU with no
configuration.

ƒ

CPU not communicating
with Ethernet Interface

ƒ

(Condition can last a
maximum of 2 minutes.)

ƒ

Use PLC Programmer configuration
software to configure the Interface
then store the configuration to the
PLC CPU.

ƒ

Make sure Interface is in the correct
slot on the baseplate.

ƒ

Power cycle the PLC.

ƒ

Clear faults and Restart Interface.

✫ OK (Slowblink)

/

/

LAN (ON/Traffic/OFF)

❍ FDX (OFF/Slowblink)

✫ STAT (Slowblink)

OK and STAT blink in unison.

D

Waiting for IP

Address

Interface’s IP address has not
been configured or has been
configured as 0.0.0.0.

ƒ

Use PLC Programmer to configure
the Interface with a non-zero IP
address.

ƒ

Use a BOOTP server to provide
Interface with a non-zero IP address.

✫ OK (Slowblink)
●/

/

LAN

(ON/Traffic/OFF)

✫ FDX (Slowblink)

●/❍ STAT (ON/OFF)

OK and SER blink in unison.

E

Maintenance

ƒ

Restart pushbutton pressed
until bottom two LEDs turn
ON.

ƒ

Station Manager MAINT
command issued.

ƒ

Internal System Error when
Interface was Operational
caused a restart and
entrance into Maintenance.

ƒ

If you did not intend to enter
Maintenance press the Restart
pushbutton for less than 5 seconds.
This clears the Maintenance request.

ƒ

Examine PLC Fault Table for clues.*

ƒ

If you need to use the Station
Manager to troubleshoot a problem,
see GFK-1186, TCP/IP Ethernet
Communications for the Series 90
PLC Station Manager Manual.

● OK (ON)
●/

/

❍ LAN

(ON/Traffic/OFF)

●/❍ FDX (ON/OFF)

1

●/❍ STAT (ON/OFF)

1

FDX should be ON if Full

Duplex mode is activated;
otherwise, it should be OFF.

F

Operational

ƒ

If the LAN LED is OFF,
the problem may be:

ƒ

Network cable or
transceiver not connected to
Interface or bad transceiver.

ƒ

Network cable not
terminated properly.

ƒ

SQE not enabled on
transceiver.

ƒ

If the STAT LED is OFF,
an exception condition has
occurred.

ƒ

Connect cable and transceiver
properly. Replace transceiver.

ƒ

Terminate network cable properly.

ƒ

Set SQE ON on transceiver in accord
with manufacturer’s instructions.

ƒ

Examine PLC Fault Table to find out
why the STAT LED is OFF. *

* Identify the PLC fault message using the PLC Programmer, then refer to Table 8-1 in Chapter 8 for corrective actions.