2-20

TCP/IP Ethernet Communications for the Series 90™ PLC User's Manual

May 2002

GFK-1541B

2

CPU364 Labels

Default Station Address Label

The Default Station Address label lists the MAC address to be used by this Interface.

Serial Number Label

The Serial Number Label indicates the serial number of this Interface.

Replaceable Surface Mount Fuse

A user-replaceable fuse is provided on the DC power that is supplied by the Ethernet Interface to
the AAUI network port for use by an external transceiver. Replace only with a surface mount
2.69x2.69x6.1mm, 125V, 1A, fast-acting fuse (such as catalog number R454 001 made by
LittelFuse; http://www.littelfuse.com). You may order this fuse from GE Fanuc. The part
number is 44A725214-001.

Removing and Installing the Fuse

1

.

Be sure the Series 90-30 PLC baseplate power is OFF.

2

.

Remove the CPU364 module from the baseplate.

3

.

Remove the front shroud. The CPU364 is a two-board module, the fuse is located between
the AAUI port and the 10Base-T port. See Figure 3-1.

4

.

Remove the blown fuse using a pair of small, bent-nose pliers.

5

.

Insert the new fuse. Make sure the fuse is seated properly.

6

.

Replace the front shroud and re-insert the CPU364 module.

7

.

Restore power to the baseplate.