COMMREQ Status Word:

The Ethernet Interface updates the CRS word to show success or

failure of the command. Command words 3 and 4 specify the PLC memory location of the CRS
word.

(Word 3) COMMREQ Status Word Memory Type:

This word specifies the memory type for the

CRS word. The memory types are listed in the table below:

Type

Value

(Decimal)

Value

(Hex.)

Description

%R

8

08H

Register memory (word mode)

%AI

10

0AH

Analog input memory (word mode)

%AQ

12

0

CH

Analog output memory (word mode)

%I

16
70

10H
46H

Discrete input memory (byte mode)
Discrete input memory (bit mode)

%Q

18
72

12H
48H

Discrete output memory (byte mode)
Discrete output memory (bit mode)

%T

20
74

14H

4AH

Discrete temporary memory (byte mode)
Discrete temporary memory (bit mode)

%M

22
76

16H

4CH

Discrete momentary internal memory (byte mode)
Discrete momentary internal memory (bit mode)

%G

56
86

38H
56H

Discrete global data table (byte mode)
Discrete global data table (bit mode)

(Word 4) COMMREQ Status Word Address Offset:

This word contains the offset within the

memory type selected. The status word address offset is a zero-based number. For example, if
you want %R1 as the location of the CRS word, you must specify a zero for the offset. The offset
for %R100 would be 99 decimal. Note, however, that this is the only zero-based field in the
Channel commands.

(Word 5):

Reserved. Set to zero.

(Word 6):

Reserved. Set to zero.

(Words 7 and up) Data Block:

The Data Block defines the Channel command to be performed.

For information on how to fill in the Channel command information, see the next section.

www.cadfamily.com EMail:[email protected]