Establish Read Channel (2003)

The Establish Read Channel command requests that a channel be associated with a remote PLC
and that data from the remote PLC be transferred (periodically) to the local PLC. The Command
Block specifies the period, the number of reads from the server (remote PLC) to perform, and the
timeout allowed in waiting for each transfer to complete. The first read is performed
immediately, regardless of the period specified.

Example 1 Command Block–Basic Example

Establish a channel (Channel 5) to a remote PLC at IP address 10.0.0.1. Return the COMMREQ
Status word to %R10. Read remote PLC registers %R50–%R57 to local PLC registers %R100–
%R107. Repeat the read 10 times, once every 7 seconds, with a timeout of 500 ms for each read.

Dec (Hex)

Word 1

00017 (0011)

Length of Channel command Data Block (17–25 words)

Word 2

00000 (0000)

Always 0 (no-wait mode request)

Word 3

00008 (0008)

Memory type of CRS word (%R)

Word 4

00009 (0009)

CRS word address minus 1 (%R10)*

Word 5

00000 (0000)

Reserved

Word 6

00000 (0000)

Reserved

Word 7

02003 (07D3)

Establish Read Channel command number

Word 8

00005 (0005)

Channel number (5)

Word 9

00010 (000A)

Number of read repetitions (read 10 times)

Word 10

00003 (0003)

Time unit for read period (3=seconds)

Word 11

00007 (0007)

Number of time units for read period (every 7 seconds)

Word 12

00050 (0032)

Timeout for each read (500 ms)

Word 13

00008 (0008)

Local PLC - Memory type at which to store data (%R)

Word 14

00100 (0064)

Local PLC - Starting address at which to store data

(%R100)

Word 15

00008 (0008)

Remote PLC - Memory type from which to read data (%R)

Word 16

00050 (0032)

Remote PLC - Starting address from which to read data

(%R50)

Word 17

00008 (0008)

Remote PLC - Number of memory units (8 registers)

Word 18

00001 (0001)

Remote PLC - Network Address type (IP Address)

Word 19

00004 (0004)

Remote PLC - Network Address length in words (4)

Word 20

00010 (000A)

Remote PLC - Register 1 of IP address (10)

Word 21

00000 (0000)

Remote PLC - Register 2 of IP address (0)

Word 22

00000 (0000)

Remote PLC - Register 3 of IP address (0)

Word 23

00001 (0001)

Remote PLC - Register 4 of IP address (1)

Word 24–27

Remote PLC - Program Name (needed for access to

remote %P or %L) (zero-terminated and padded)

Word 28–31

Remote PLC - Program Block (needed for access to

remote %L) (zero-terminated and padded)

* Word 4 (CRS word address) is the only zero-based address in the Command Block. Only this

value requires subtracting 1 from the intended address.

The term local PLC is
used here to identify the
client PLC—the PLC
that initiates the
communications
request.

The term remote PLC is
used here to identify the
server PLC—the PLC
that responds to the
communications
request.