TCP/IP Ethernet Communications for the Series 90™ PLC User's Manual

May 2002

GFK-1541B

C

Updating Firmware Under Windows

You will need an IBM compatible PC running Windows 95, Windows 98, or Windows NT 4.0,
equipped with a 3.5 inch high-density diskette drive and an RS-232 serial port. The firmware
update process requires 500 KB of hard drive space. If you are using Windows 3.xx or Windows
NT 3.51, follow the instructions in the “Updating Firmware under DOS” section.

To install the new firmware, perform the following steps

1.

Connect one of the serial ports on your PC to the Software Loader Port on your Ethernet
Interface.

ƒ

For the IC693CMM321 Series 90-30 Ethernet Interface (AAUI-only Type) and for the
IC697CMM742 Series 90-70 Ethernet Interface (Type 2), use cable assembly
IC690ACC901.

ƒ

For the IC693CMM321 Series 90-30 Ethernet Interface (10Base-T Type) and for the
IC693CPU364 Embedded Ethernet Interface, use serial cable IC693CBL316A.

Exit any application that is using this PC serial port (such as PLC programming software).
Connect the proper serial cable to the Ethernet Interface and to the PC. See Appendix B,
“Communications Ports Characteristics”, for more information.

2.

Insert the update diskette into the diskette drive of your PC.

3.

Invoke the WinLoader Utility by either double clicking its icon displayed by Windows
Explorer, or use the “Run…” selection of the Start menu and specify the location of the
WinLoader Utility, e.g. “a:\winloader”.

4.

The WinLoader Utility uses the COM1 port of your PC by default. If you connected your
cable to COM1, skip the rest of this step. If you connected your cable to a different com port,
use WinLoader’s “COM Port” drop-down box to select the proper com port.

5.

In most cases, you should not need to adjust the serial port settings that the WinLoader
Utility uses. No adjustment is necessary if your Ethernet Interface’s Software Loader port
configuration is set for:

ƒ 19,200 baud
ƒ ODD parity
ƒ 8 data bits
ƒ 0 modem turnaround time

If other settings are used, you must modify the serial port configuration used by the Firmware
Update Utility to use the same serial configuration as your Interface each time you run the
Firmware Update Utility.

To do this, click the “Settings” button and select the matching serial port settings. Then click
“OK” to activate the new settings.

6.

To prepare the Ethernet Interface to receive a firmware load, follow the steps below:

With your Ethernet Interface installed in a PLC, powered on and functioning, press the restart
button near the top of your Ethernet Interface and hold it down for five seconds. When the
button is first pressed, all green LED indicators will go out. After five seconds, the bottom
LED will go on, indicating that your Interface will enter the load state when the button is
released. Release the button. All LEDs will flash briefly and then begin to blink
simultaneously. At this point, your Interface is ready to accept a firmware load. (Note: If
you hold the restart button down too long, the Ethernet Interface will enter maintenance