Chapter 7 Troubleshooting

7-5

7

PLC Fault Table Descriptions

PLC Fault

User Action

Backplane communications with PLC fault;
lost request

User Action: Check to make sure you are not sending
COMMREQs faster than the Ethernet Interface can
process them. If problem persists, contact GE Fanuc
Automation - NA.

Bad local application request; discarded
request

User Action: Check for valid COMMREQ command
code. If problem persists, contact GE Fanuc Automation -
NA.

Bad remote application request; discarded
request

User Action: Try to validate the operation of the remote
node. If problem persists, contact GE Fanuc Automation -
NA.

Can’t locate remote node; discarded request

Error reported when message received where IP/MAC
address cannot be resolved. Error may indicate that
remote host is not operational on the network.
User Action: Check that remote host is operational on
network and its addresses are correct.

Comm_req - Bad task ID programmed

Message from PLC for unknown Ethernet Interface task.
User Action: Check COMMREQ function block.

Comm_req - Wait mode not allowed

User Action: Check COMMREQ to make sure sent in no-
wait mode.

Config’d gateway addr bad; can’t talk off local
net

Error in configuration. Verify IP address, Subnetwork
Mask, and default Gateway IP address are
correct.

Connection to remote node failed; resuming
without it

Underlying communications software detects error
transferring data; resuming. If persistent error,
check connection to LAN and operation of remote node.

LAN controller fault; restart LAN I/F

User Action: HW fault, perform power cycle. If problem
persists, contact GE Fanuc Automation - NA.

LAN controller Tx underflow; attempt
recovery

Internal system error. User Action: If problem
persists, contact GE Fanuc Automation - NA.

LAN controller underrun/overrun; resuming

Internal system error. User Action: If problem
persists, contact GE Fanuc Automation - NA.

LAN data memory exhausted - check parms;
resuming

The Ethernet Interface does not have free memory
to process communications. User Action: If
problem persists, contact GE Fanuc Automation - NA.

LAN duplicate MAC Address; resuming

A frame was received in which the source MAC
Address was the same as this station’s MAC Address. All
stations on a network must have a unique MAC address.
Immediately isolate the offending station; it may be
necessary to turn it off or disconnect it from the network.
This station remains Online unless you intervene to take it
Offline.

LAN controller fuse blown; off network

(Series 90-70 Ethernet Interface (Type 2) and Series 90-
30 CPU364)

The network port fuse is blown; port is

unusable. Isolate and correct the cause of the problem,
then replace the fuse or the Ethernet Interface.