4-12

TCP/IP Ethernet Communications for the Series 90™ PLC User's Manual

May 2002

GFK-1541B

4

Command 3003 Example 1

Read four Input Registers from Address 30200 in the remote Modbus/TCP device. Store the
registers at location %R20. Return the COMMREQ Status word to %R10.

Dec (Hex)

Word 1

00008 (0008)

Length of Channel command Data Block

Word 2

00000 (0000)

Always 0 (no-wait mode request)

Word 3

00008 (0008)

Memory type of CRS word (%R)

Word 4

00009 (0009)

CRS word address minus 1 (%R10) *

Word 5

00000 (0000)

Reserved

Word 6

00000 (0000)

Reserved

Word 7

03003 (0BBB)

Read from a Modbus/TCP Device

Word 8

00006 (0006)

Channel number (6)

Word 9

00004 (0004)

Modbus Function Code

Word 10

00008 (0008)

Local PLC Memory Type

Word 11

00020 (0014)

Local PLC Starting Address

Word 12

00200 (00C8)

Address in the Remote Server

Word 13

00004 (0004)

Number of Registers in the Remote Device

Word 14

00001 (0001)

Unit Identifier

* Word 4 (CRS word address) is the only zero-based address in the Command Block. Only this

value requires subtracting 1 from the intended address.

(Word 7) Channel Command Number:

Word 7 identifies the COMMREQ as a Read Data from

Modbus/TCP Device command block.

(Word 8) Channel Number:

Word 8 identifies the channel number previously allocated for

communication with the remote Modbus/TCP server.

(Word 9) Modbus Function Code:

Word 9 specifies Modbus Function Code 4, Read Input

Registers.