TCP/IP Ethernet Communications for the Series 90™ PLC User's Manual

May 2002

GFK-1541B

5

Exchange Status Word Error Codes

The following table shows the error codes that can be written to the Exchange Status word.

Value

(Dec.)

Produced /

Consumed

Error

Description

0

P/C

No new status

event has

occurred.

Produced: Initial value until the first producer period refresh occurs.
Consumed: The data has not been refreshed since the previous

consumption scan and the consumer timeout has not expired.

1

P

No error

currently exists.

The exchange is producing data.

1

C

No error, data

consumed.

The data has been refreshed on schedule since the previous

consumption.

3

C

SNTP error. .

The Ethernet Interface in the producer is configured for network time

synchronization, but is not synchronized to an SNTP server. The data

has been refreshed on schedule.

4

P/C

Specification

error.

Produced: During exchange configuration*, an invalid configuration

parameter was received by the Ethernet Interface or an error occurred in

communication with the PLC CPU.
Consumed: Same as Produced, or the size of a received packet for this

exchange definition did not match the expected size.

6

C

Refresh timeout

without data.

The exchange’s timeout period is configured to a non-zero value and the

data has not been refreshed within the timeout period.

7

C

Data after

refresh timeout.

The data has been refreshed since the previous consumption, but was

not refreshed within the timeout period.

10

P/C

IP Layer not

currently

initialized.

This status can be set during exchange configuration* if the Ethernet

Interface detects that it cannot currently access a network (cable not

connected, hardware failure, etc.) This is a temporary status that may

change if successful network access becomes possible.

12

P/C

Lack of

resource error.

Local resources are not available to establish the exchange. This error

can only occur during exchange configuration*. The PLC Fault Table

should be examined to obtain more detail on the specific error.

16

P

Name

Resolution in

progress.

A local produced exchange definition has specified a name for the

consumer address and the local Ethernet Interface is awaiting a response

from a remote name server following exchange configuration*. This is a

temporary status that will change when the name resolution completes. If

successful, the status will become 0 (No New Data); if unsuccessful, the

status will become 4 (Specification Error).

18

P/C

Loss of Ethernet

Interface error.

This error can occur if the CPU no longer recognizes the Ethernet

Interface within the PLC rack. A loss of module PLC Fault Table entry will

also be present. The error can also occur if the module in the given slot of

the PLC rack does not match the module specified in the configuration

(configuration mismatch).

22

P/C

Ethernet

Interface does

not support

EGD.

The revision level of the Ethernet Interface does not support global data.

26

P/C

No Response

from Ethernet

Interface.

Did not respond to establish exchange request. This fault can only occur

during exchange configuration*.

28

P/C

Failed to create

an exchange.

An error occurred (other than a resource error, no response or loss of

Ethernet Interface) during exchange configuration*. A PLC Fault Table

entry is provided for additional information about the fault.

* Exchange configuration occurs when either 1) Hardware Configuration containing EGD is
stored to the PLC, 2) a PLC containing EGD configuration powers up, or 3) an Ethernet Interface
configured for EGD is restarted.

www.cadfamily.com EMail:[email protected]
The document is for study only,if tort to your rights,please inform us,we will delete

Advertising