Chapter 5 Ethernet Global Data

5-19

5

Example 3: EGD Configuration Using a Symbolic Name to Identify Consumers

There are three PLCs in this more complex EGD system using three Ethernet Global Data
exchanges. PLC1 contains two Ethernet Interfaces (designated A and B), one of which is both a
producer and a consumer. PLC2 is a consumer only. And PLC3 is both a producer and a
consumer. The Adapter Names are used as the symbolic names to identify the consumer PLCs.
No aliases have been configured, so DDP name resolution will be used. (See “Name Resolution”
in the chapter: “Network Administration Support”, for more information.) Network-synchronized
time stamping is not used. The identification of the PLCs and the details of the exchange are
shown in the tables below.

PLC1

PLC2

PLC3

P
C

P
C

P

C

Exchange ID = 3

Exchange ID = 1

Exchange ID = 2

A B

Producer/Consumer Information for Entire EGD System – EXAMPLE 3

Ethernet Interface(s)

Your Name for

the PLC

(Equipment

Folder Name)

P

C

Local

Producer ID

Network

Adapter Name

CCU Device

Name

IP Address*

PLC1

X

X

0.0.0.1

PLC1_A

PLC1_A

10.0.0.23

PLC1

X

0.0.0.1

PLC1_B

PLC1_B

10.0.0.34

PLC2

X

0.0.0.2

PLC2

PLC2

10.0.0.41

PLC3

X

X

0.0.0.3

PLC3

PLC3

10.0.0.50

P=Producer C=Consumer * Use your own IP addresses here.

Produced Exchanges Information – EXAMPLE 3

Local

Producer ID

Exchange

ID

Local Adapter Name

Consumer

Type

Consumer

Address

Send
Type

Producer

Period

Reply

Rate

Status

Word

0.0.0.1

1

PLC1_A

Name

PLC3

Always

1000

0

Stat1

0.0.0.1

3

PLC1_B

Name

PLC2

Always

1000

0

Stat3

0.0.0.3

2

PLC3

Name

PLC1_A Always

1000

0

Stat2

Variable List for Produced Exchanges – EXAMPLE 3

Local

Producer ID

Exchange

ID

Var

#

Name

Address

Length

Type

Description

0.0.0.1

1

1

Conveyor1 %R00100

5

WORD

Conveyor1 in PLC1

0.0.0.1

3

1

Conveyor2 %R00105

5

WORD

Conveyor2 in PLC1

0.0.0.3

2

1

Vat1

%R00300

10

WORD

Vat1 in PLC3

0.0.0.3

2

2

Vat2

%R00310

10

WORD

Vat2 in PLC3