Chapter 5 Ethernet Global Data

5-3

5

Producer

The producer is the device that will periodically produce new samples of data from its local
internal memory. The producer is uniquely identified by the Producer ID.

The Producer ID is a dotted-decimal number (for example, 0.0.0.1). Although this number is in
IP address form, it is not used as an IP address; it is used simply to uniquely identify a particular
PLC on the network. Note that in the case where a Producer ID identifies a PLC producing the
exchange, it doesn’t matter how many Ethernet Interfaces may be installed in that PLC. For
example, a Series 90-70 PLC only has one Producer ID even if it has two or more Ethernet
modules installed.

Configuring the Producer ID

The Producer ID is configured via the Local Producer ID field in the Ethernet Global Data Rack
Operation of the PLC programming software. A default Producer ID value is provided. You can
change the value of the Producer ID from the default value to any number in dotted-decimal form.
To ensure uniqueness on the network, the default value is:

Series 90-70 PLCs

The same as the IP address of the Ethernet Interface physically closest to the CPU in the rack.

Series 90-30 PLCs

The same as the IP address of the Embedded Ethernet Interface.

Note

When you configure the producer of Ethernet Global Data, you must also
supply the adapter name of the Ethernet Interface from which the exchange will
flow. This name is configured using the PLC programming software (if
supported). You need to specify the adapter name because in Series 90-70
PLCs, more than one Ethernet Interface that supports Ethernet Global Data can
be installed.

For a Series 90-30 CPU374, the adapter name is specified as a rack and a slot
rather than as a symbolic name.

Consumer

The consumer is the PLC or other device that will update its local internal memory based on the
data in an exchange. The consumer is identified at the producer by a Group ID, an IP address, or
a symbolic name. These identifiers refer to the specific Ethernet Interface in the consumer. (For
Series 90-70 PLCs there can be more than one Ethernet Interface that supports Ethernet Global
Data installed in the PLC.)

Group ID: This method is typically used when you want more than one consumer to receive the
same exchange from a producer. See the topic “Group Usage” for more information.

IP Address: This method is used when you want to identify the consumer’s Ethernet Interface
using an IP address.

Symbolic Name: This method is used when you want to use local table, DDP, or DNS name
resolution to acquire the consumer’s IP address. See “Name Resolution” in the chapter:
“Network Administration Support”, for more information.