FANUC Robotics America GFK-1541B User Manual

Page 52

Advertising
background image

GFK-1541B

Chapter 2 Installation

2-39

2

LED Pattern

Where Stopped

Possible Cause

Corrective Actions

❍ EOK (OFF)

❍ LAN (OFF)

❍ STAT (OFF)

A

Hardware
Failure

Fatal Hardware Error.

ƒ

Make sure the PLC has power.

ƒ

Examine PLC Fault Table for clues.

ƒ

Recheck PLC Programmer

configuration.

ƒ

Power off baseplate, inspect the

Interface for loose components,
reseat the module, and Restart.

ƒ

If the problem persists, replace the

PLC hardware.

✫ EOK (Slowblink)

✫ LAN (Slowblink)

✫ STAT (Slowblink)

All LEDs blink in unison.

B

Software
Loader

Software corrupt.

Connect a PC Software Loader and load
new software. See Appendix C.

✫ EOK (Slowblink)

❍ LAN (OFF)

❍ STAT (OFF)

C

Waiting for
Configuration
from PLC

ƒ

Did not configure slot using the

PLC Programmer.

ƒ

CPU not communicating with

Ethernet Interface.

(Condition can last a maximum of
2 seconds.)

ƒ

Use the PLC Programmer

configuration software to configure
the Interface then store the
configuration to the PLC CPU.

ƒ

Power cycle the PLC.

ƒ

Clear faults and Restart Interface.

✫ EOK (Slowblink)

/

✲/❍

LAN

(ON/Traffic/OFF)

✫ STAT (Slowblink)

EOK and STAT blink in unison.

D

Waiting for IP
Address

Interface’s IP address has not been
configured or has been configured
as 0.0.0.0.

ƒ

Use the PLC Programmer to

configure the Interface with a non-
zero IP address.

ƒ Assign IP address over network

●EOK (ON)

/

✲/❍

LAN (ON/Traffic/OFF)

/

STAT(ON/OFF)

E

Operational

ƒ

If the LAN LED is OFF,
the problem may be
network cable not
connected

ƒ

If the STAT LED is OFF, an
exception condition has
occurred.

ƒ

Connect cable.

ƒ

Examine PLC Fault Table to find out

why the STAT LED is OFF.