2. Processes and functions

2-13

Electronic Refrigerant Control Valve

This valve allows very precise and smooth control of the amount of refrigerant flow in the
system. Since the valve is operated by a step motor, the control circuits can open or
close it in very exact amounts, so the degree of heating or cooling can be changed by
just a little, or changed very quickly or slowly.

(Completely close …… 0 step)

(Full open................ 480 step)

Fuzzy Control
Fuzzy Control is a controlling system to control electronic refrigerant control valve using
fuzzy logic. It regulates the functions of heating and cooling, as well as some of the
processes inside the unit, by taking account of many different conditions of temperature,
fan speed, etc. These control circuits work automatically to send just the right amount of
refrigerant through the Electronic Refrigerant Control Valve.

2-14

Compressor Discharge Gas Temperature

(A)

Cooling

Indoor temp. (°F)

68 – 77

79 – 82

84 – 90

Outdoor temp. (°F)

55 or below

57 – 61

81 – 95

97 – 109

Compressor discharge
gas temp. (°F)

104 – 176

104 – 194

140 – 212

158 – 221

(B)

Heating (Except During Defrosting)

Indoor temp. (°F)

64 – 70

72 – 77

79 – 86

Outdoor temp. (°F)

32 or below 34 – 50 32 or below 34 – 50

52 – 70 32 or below 34 – 50

52 – 70

Compressor discharge
gas temp. (°F)

104 – 176 122 – 194 122 – 194 122 – 212 140 – 221 122 – 194 140 – 212 158 – 221

Operate the unit at least 30 minutes to stabilize the discharge temperature.

The above discharge temperature was measured with a 15m tubing length.
The temperature may vary with tubing length.

Model

Min. open

Max. open

HEAT

COOL

24 type

100 step

100 step

36 type

90 step

90 step

480 step

42 type

100 step

100 step