6 condensing temperature control (cooling) – Sanyo KH2442 / CH2442 User Manual

Page 128

Advertising
background image

II - 8

SM830082

1

2

3

4

Section

5

2. Processes and functions

Fig. 9

2-6

Condensing Temperature Control (Cooling)

Condensing temperature is controlled by the outdoor heat exchanger coil temperature as
sensed by sensor C2.

Chart Explanations and notes

This chart shows how the outdoor fan speed and the electronic refrigerant control valve
react to coil temperature to control condensing temperature.

Sensor C2 is located in the middle of the outdoor unit heat exchange coil.

When C2 rises above 140°F the electronic refrigerant control valve opens at 50 steps/30
seconds, and the outdoor fan speed is forced to change to high (H) until C2 falls below
131°F.

140

131

OUTDOOR UNIT

COIL TEMP. C2

(

°

F)

OUTDOOR FAN

SPEED

ELECTRONIC REF.

CONTROL VALVE

H, M or L

H, M or L

FORCED

H

1926_THS_I

OPEN