4. Service procedures

1

2

3

4

Section

SM830082

IV - 14

10) Symptom: LCD on the remote controller displays “CHECK P02”. (Compressor / outdoor

fan protection thermostat operation warning / power supply voltage
abnormality)

Yes

No

Yes

No

2099_THS_I

Start

Is the outdoor fan wire winding
protection thermostat (49FO) off?

Replace the outdoor fan.

Is there connector contact defect?

Replace the outdoor unit PCB.

Correct the connection

Yes

No

No

No

Replace the outdoor unit PCB.

Is there 230-208 V AC between
CN19-9 and CN19-7 on the
outdoor unit PCB?

Yes

Replace the outdoor unit PCB.

Is the high pressure switch
(63 PH) off?

Yes

Replace the fuse.

Is the fuse on the outdoor unit
PCB blown (F1 and F2)?

• No refrigerant
• High load
• 4-way valve defect
• Clogged refrigerant circuit
• Electronic refrigerant control valve
defect (indoor unit)

Yes

No

Check the power breaker etc.
and repair.

Is the power supply to the outdoor
unit normal?
(Voltage / defective phase?)