Sanyo KH2442 / CH2442 User Manual

Page 187

Advertising
background image

1

2

3

4

Section

SM830082

IV - 31

SM830082

4. Service procedures

(2)

Checking the Protective Devices

Disconnect the connector, which consists of P (plug) and S (socket) when you want to
check the protective device.

Then check continuity among plug’s (and/or socket’s) terminal as in Fig. IV-18.

Normality of the protective device can be judged by the following table.
The Protective Device is proved normal if there is a continuity between terminals.

1

1

1

1

1

Indoor fan motor thermal protector (49FI) . . . . . . Indoor unit

Disconnect the connector which leads to the indoor fan motor (FMI).

Check the socket’s terminals.

2

2

2

2

2

Compressor motor thermal protector . . . . . . Outdoor unit

Disconnect the wires from terminals of compressor.

Check the terminals of compressor.

3

3

3

3

3

Outdoor fan motor thermal protector (49FO) . . . . . . Outdoor unit

Disconnect both the connector which leads to the outdoor fan motor (FMO).

Check socket’s terminal.

socket

Multimeter

0642_X_S

Fig. IV-18

Advertising