4. Service procedures

1

2

3

4

Section

SM830082

IV - 10

2)

Symptom: LCD on the remote controller displays “CHECK E01”. (Unusual

communication between remote controller and indoor unit.)

OK

No

No

Yes

Yes

NG

2096_THS_I

Start

Remote controller judges itself
with self-diagnostic functions

Replace the remote controller.

Correct the wiring.

Open the inspection pin.

Is there an open or a contact
defect in the No. 1 line of the
remote controller?

No

Yes

Yes

Is there 230 -208 V AC between
U1 and U2 of terminal plate?

Mis-wiring between the power
supply line and indoor/ outdoor
unit operation lines.

Correct the wiring, and pull out the
socket connected to the OC plug
to replace with the EMG plug.

Is the indoor unit PCB’s inspection
pin shorted?

Replace the indoor unit PCB.

3) Symptom: LCD on the remote controller displays “CHECK E02”. (Unusual

communication between remote controller and indoor unit)

OK

NG

2097_M_I

Start

Replace the remote controller.

Remote controller judges itself with
self-diagnostic functions.

Replace the indoor unit PCB.