2. Processes and functions

2-2

Cold Draft Prevention (Heating Cycle)

The cold draft prevention function controls indoor fan speed so a strong draft of cold air will
not blow out before the indoor heat exchange coils have warmed up.

STANDBY shows on the remote controller when the indoor fan speed is LL (very
low) or OFF. This condition occurs in the following 3 cases:
• During Thermo OFF (refer to 2-1 B). Room Temperature Control, Heating)

• During the defrosting operation (refer to 2-10 Defrosting Control, Heating)

• Until either the coil temperature E2 reaches 81°F or when a maximum of 6 minutes

has past.

The indoor fan motor operates in L instead of LL for 3 seconds as it starts to give
the fan an initial boost.

Chart Summary and Explanations

The main idea of this chart is to show that the indoor fan speed increases and gets closer to
the set fan speed as the coil temperature E2 rises.

The indoor unit’s coil temperature is taken from sensor E2 located in the middle of the indoor
heat exchange coil.

The dotted line shows that the indoor fan motor is OFF. When the temperature at sensor E2
falls below 50°F, the indoor fan motor stops running.

Fig. 3

92

88

81

77

50

SET
FAN
SPEED

AUTO OR H

M

L

LL

LL/OFF

LL

L

L

L

LL

LL/OFF

LL

L

M

M

LL

LL/OFF

LL

L

M

H

MAX. 6 MINUTES

“STANDBY”
INDICATOR

INDOOR UNIT

COIL TEMP.

E2 (

°

F)

LL= Very low speed
L= Low speed

M= Medium speed
H= High speed

“STANDBY” APPEARS

1135_THS_I