2. Processes and functions

2-10

Defrosting Control, Outdoor Heat Exchanger Coil (Heating)

When the outdoor temperature is low, frost may form on the outdoor heat exchanger coil.
When this occurred, the defrosting system operates. The microprocessor in the outdoor unit
monitors the relationship between the temperature of the outdoor heat exchanger coil and the
outdoor temperature so it can defrost when necessary.

Fig. 13

Fig. 14

COMPRESSOR

OFF OR LL

OFF

OR LL

Release of
Defrosting

Defrosting
Start

SOLENOID COIL
(4 WAY VALVE)

OUTDOOR FAN
(H OR L)

INDOOR FAN
(SET SPEED)

“STANDBY”
INDICATOR

MAX. 9 MINUTES

1 MINUTE

1 MINUTE

ON

ON

ON

ON

ON

ON

ON

“STANDBY” APPEARS

0442_M_S

Time Chart for Defrosting

During the defrost cycle, STANDBY appears on the remote controller.

*......Cold Draft Prevention may operate occasionally

Occurs either when the temperature of C1 (the outdoor
heat exchanger coil) has reached 50

°

F or above,

or when the maximum defrosting time (9 minutes)
has elapsed.

Refer to time chart.

*Minimum continuous operating time by defrosting is 48 minutes (= 15 + 8 + 25).

Release of defrosting

Defrosting

Stand by time for defros:
25 minutes

Flow of Defrosting

Heating operation

No counting time for detecting
frost : 15 minutes

Detecting the frost

OUTDOOR COIL
TEMP. C1 (

°

F)

Y

“RELEASE OF
DEFROSTING”
RANGE

50

7.3

50

OUTDOOR AIR TEMP.

(

°

F)

X

27

18

The area below the heavy line
is the frost detection area.

–4

Either continuous 8 minutes or cumulative 60 minutes
are required to detect frost in the “Frosting” range.

1143_THS_I