4. Service procedures

1

2

3

4

Section

SM830082

IV - 38

(7) Automatic Address Setting Method

(8) Displaying Indoor / Outdoor Unit Com-

bination Numbers

Display the indoor / outdoor unit address after auto-

matic address setting.

(1)

When installing multiple units, match the indoor

unit address numbers and the outdoor R.C.

address numbers and display them at an easy-to-

check location (near the nameplate) with an oil-

based magic marker or other indelible marker so

that the individual indoor and outdoor unit combi-

nations can be checked.

Example:

Outdoor Unit 1 – Indoor Units 1-1, 1-2, 1-3, ....

Outdoor Unit 2 – Indoor Units 2-1, 2-2, 2-3, ....

(2)

This is necessary for maintenance. Always label

these.

*Check indoor unit address with the remote

controller. Press the

button for at least 4

seconds and check the indoor unit address with

the

button. (Each time you press the

button, the address changes 1-1, 1-2, ...

2-1, 2-2, ...) The fan for only the selected indoor

unit turns on at high speed, so check which

indoor unit runs and label the indoor unit address.

(If there is 1 outdoor unit, the addresses are 1-1,

1-2, ...)

When you press the

button again, the system

returns to normal remote control mode.

— For group control and central control with multiple
outdoor units —

Carry out automatic address setting with the
remote controller.
(1)

All auto. address operation

1

Press the

and

(

) buttons at

the same time for more than 4 seconds.

2

Press the

button after confirming the

CODE No. AA (CODE No. AA: All Auto.
address operation).

After addresses are automatically set in
order for the outdoor units from No. 1 to No.
30, the system returns to the normal
stopped state.

(2)

Individual auto. address operation for each
refrigerant circuit

1

To select each refrigerant circuit individually
and set addresses automatically, press the

and

(

) buttons at the same

time for more than 4 seconds, then press
the

,

( ) button once to set

CODE No. A1.
(CODE No. A1: Auto. address operation)

2

Select R.C. No. which you want to execute
the auto. address operation with
button.

3

Press the

button. The auto. address

operation will start. CODE No. changes from
flashing to ON state.

4

If the error is happened during the operation,
the alarm message will display. Check and
remove the cause. If you want to interrupt
the operation, press the

button then the

unit stands in waiting mode (Press the
button).

5

If the auto. address operation finishes, the
display will disappear.

6

Execute the operation of the other R.C. line
in the same way by following the above
steps

2

to

3

.

7

Complete the auto. address operation by
pressing the

button.

Required time for auto. address operation:

In case of group control : a few minutes for each R.C.
In case of central control : max. about 20 min. for

each R.C.