4. Service procedures

1

2

3

4

Section

SM830082

IV - 44

(12) Checking procedure for each PC Board

The indoor and outdoor PCBs have functions to check the signal transmission and reception of the
serial circuit and to check the microcomputer operation. (Self-diagnosis function)

Precautions required when checking

1. After turning off the power to the indoor (outdoor) unit, remove the inter-unit control wiring (U1-U2)

and create a short-circuit between U1 and U2.

2. Short the CHECK PIN on the PC board of the indoor (outdoor) unit and turn on the power.

3. When checking the Outdoor controller, remove the compressor wiring from the compressor

electromagnetic contactor.

4-1. Checking the serial circuit

Indoor controller: A lighted LED indicates normal. A blinking LED indicates abnormal.
Outdoor controller: Blinking LEDs (D11 and D22) indicate normal. If one of the LEDs (D11 and D22)

goes off, it indicates abnormal.

4-2. Checking microcomputer operation

When the microcomputer works normally, the relays are switched in sequence as below.

Output

ON time

Indoor fan Very high fan speed (HH) 0.5 seconds

Indoor fan High fan speed (H)

0.5 seconds

Indoor fan Low fan speed (L)

0.5 seconds

Indoor fan Very low fan speed (LL)

0.5 seconds

Flap motor

0.5 seconds

Drain pump

0.5 seconds

Operation order

Electric heater

0.5 seconds

Operation signal

0.5 seconds

In a lump

0.5 seconds

Electronic control valve A

0.5 seconds

Electronic control valve B

0.5 seconds

Electronic control valve.A

0.5 seconds

Electronic control valve B

0.5 seconds

Indoor controller

Output

ON time

Outdoor fan High fan speed (H)

0.5 seconds

Operation order

Outdoor fan Low fan speed (L)

0.5 seconds

4-way valve

0.5 seconds

Compressor

0.5 seconds

Outdoor controller