Specifications, 2 major component specifications (a) indoor unit – Sanyo KH2442 / CH2442 User Manual

Page 19

Advertising
background image

I - 15

SM830082

1

2

3

4

5

1. Specifications

MODEL No.

TH2442

Source

230 - 208 V / 1 phase / 60 Hz

Remote controller (Option)

RCS - SH80UA, WL

Controller P. C. B Ass'y

CR - TH2442

Control circuit fuse

250 V, 3 A

Fan (Number … diameter)

in.

(mm)

Centrifugal (4 ... 5-1/8(130))

Fan motor

Model

SR4X - 51A6P

Source

230 - 208 V / 1 phase / 60 Hz

No. of pole … r.p.m. (230 V, High)

rpm

1,179

Nominal output

W

31

Coil resistance

BRW - WHT

: 111.0

,

ORG - YEL

:

16.7

(Ambient temperature 68

°

F)

WHT - VLT

:

35.4

,

BLK

- PNK

:

23.9

VLT

- ORG

:

13.4

,

YEL

- BLK

: 136.6

Safety device

Operating temperature

Open

°

F

266

±

14.4

Close

°

F

174.2

±

27

Run capacitor

VAC,

µ

F

440 V , 1.5

µ

F

Electronic refrigerant control valve

Solenoid control model

DKV - MOZS582E0

Coil resistance

ORG - GRY

:

46

,

YEL

- GRY

:

46

(Ambient temperature 68

°

F)

RED - GRY

:

46

,

BLK

- GRY

:

46

Solenoid control valve model

IKV - 24D18

Heat exchanger

Coil

Aluminum plate fin / Copper tube

Rows … Fins per inch

3 … 14.9

Face area

ft.

2

(m

2

)

1.81 (0.168)

Auto louver motor

Model No.

MT8 - 3C

Auto louver motor … Rated

V, W, rpm

240 VAC , 3 W , 3 rpm

Coil resistance (Ambient temperature 77

°

F)

16,430

±

8 %

DATA SUBJECT TO CHANGE WITHOUT NOTICE

1-2 Major Component Specifications

(A) Indoor Unit

Advertising