1. Specifications

1-2 Major Component Specifications

(A) Indoor Unit

MODEL No.

KH2442

Source

230 - 208 V / 1 phase / 60 Hz

Remote controller (Option)

RCS - BH80UA, WL

Controller P. C. B Ass'y

CR - TH2442

Control circuit fuse

250 V, 3 A

Fan

Cross-flow

Number ... Dia. and length

in.

(mm)

1 ... O.D. 4-1/3 (110), L39 (990)

Fan motor

Model

UF4Q - 31A6P

Source

230 - 208 V / 1 phase / 60 Hz

No. of pole … r.p.m. (230 V, High)

rpm

4 ... 1,276

Nominal output

W

30

Coil resistance

BRW - WHT

: 197.2

,

ORG - YEL

:

59.1

(Ambient temperature 68

°

F)

WHT - VLT

:

41.4

,

YEL

- PNK

:

48.8

VLT

- ORG

:

22.2

,

Safety device

Operating temperature

Open

°

F

248

±

9

Close

°

F

171

±

27

Run capacitor

VAC,

µ

F

440 V , 1.8

µ

F

Electronic refrigerant control valve

Solenoid control model

DKV - MOZS582E0

Coil resistance

ORG - GRY

:

46

,

YEL

- GRY

:

46

(Ambient temperature 68

°

F)

RED - GRY

:

46

,

BLK

- GRY

:

46

Solenoid control valve model

IKV - 24D11

Heat exchanger

Coil

Aluminum plate fin / Copper tube

Rows …

3 … 12.7

Face area

ft.

2

(m

2

)

2.57 (0.24)

Louver Motor

Model

M2EA24ZA01

Rating

208 to 230 V, 60 Hz

No. of pole … rpm

8 … 3

Output

W

2.5

Coil resistance (Ambient temperature 68

°

F)

k

16.45

±

8 %

DATA SUBJECT TO CHANGE WITHOUT NOTICE

Advertising