4. Service procedures

9)

Symptom: LCD on the remote controller displays “CHECK P01”. (Indoor fan protection

thermostat operation warning)

No

No

Yes

Yes

Yes

2098_THS_I

Start

Is there 230-208 V AC between T20-1
and T20-3 on the indoor unit PCB?

Is the indoor fan wire winding
protection thermostat (49FI) off?

Replace the indoor fan.

Correct the connection

Replace the indoor unit PCB.