1. Specifications
Cooling:
Rating Conditions
: Indoor Air Temperature
80
°
F DB / 67
°
F WB
Outdoor Air Temperature
95
°
F DB
Full Load Conditions : Indoor Air Temperature
80
°
F DB / 67
°
F WB
Outdoor Air Temperature 115
°
F DB
Heating:
Rating Conditions
: Indoor Air Temperature
70
°
F DB / 60
°
F WB
Outdoor Air Temperature
47
°
F DB / 43
°
F WB
Full Load Conditions : Indoor Air Temperature
80
°
F DB / —
°
F WB
Outdoor Air Temperature
45
°
F DB / 35
°
F WB
Indoor model: XH2442 / Outdoor model: CH2442
●
Cooling
●
Heating
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
230 - 208 V / 1 phase / 60 Hz
230 - 208 V / 1 phase / 60 Hz
Rating conditions
A
0.6 - 0.6
0.9 - 0.9
9.7 - 10.1
11.2 - 11.6
kW
0.12 - 0.11
0.18 - 0.17
2.15 - 2.07
2.45 - 2.35
Full load conditions
A
0.6 - 0.6
0.9 - 0.9
11.1 - 12.0
12.6 - 13.5
kW
0.12 - 0.11
0.18 - 0.17
2.50 - 2.47
2.80 - 2.75
Starting amperes
A
1 - 1
1 - 1
66 - 60
68 - 62
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
230 - 208 V / 1 phase / 60 Hz
230 - 208 V / 1 phase / 60 Hz
Rating conditions
A
0.4 - 0.4
0.9 - 0.9
10.4 - 11.0
11.7 - 12.3
kW
0.09 - 0.08
0.18 - 0.17
2.23 - 2.20
2.50 - 2.45
Full load conditions
A
0.4 - 0.4
0.9 - 0.9
10.8 - 11.7
12.1 - 13.0
kW
0.09 - 0.08
0.18 - 0.17
2.43 - 2.40
2.70 - 2.65
Starting amperes
A
1 - 1
1 - 1
66 - 60
68 - 62
Electrical characteristics
■