2. Processes and functions

Fig. 4

2-3

Automatic Fan Speed (Indoor Unit)

(A) Cooling

By pressing the FAN SPEED button on the remote controller, the fan speed can be set at
one of four steps: AUTO., HI., MED., or LO. When set at AUTO. the indoor unit fan speed
will be automatically adjusted to the room temperature as the two charts shown below.

(B) Heating

Fig. 5

INDOOR FAN

SPEED

L

H

M

M

H

1923_M_S

ROOM TEMP.

(deg)

SET TEMP.

+3

+2

+1

H
M

: High
: Middle

L : Low

Chart Explanations and notes

When the fan speed changes, it keeps the speed step for at least 3 minutes, even if the
temperature changes to another speed step during the time.

INDOOR FAN

SPEED

H

L

M

M

H

1924_M_S

ROOM TEMP.

(deg)

SET TEMP.

–2

–4

H
M

: High
: Middle

L : Low

Chart Explanations and notes

When the fan speed changes, it keeps the speed step for at least 1 minute, even if the
temperature changes to another speed step during the time.