Specifications, 2 major component specifications (a) indoor unit – Sanyo KH2442 / CH2442 User Manual

Page 18

Advertising
background image

I - 14

SM830082

1

2

3

4

5

1. Specifications

MODEL No.

XH4242

Source

230 - 208 VAC / 1 phase / 60 Hz

Remote controller (Option)

RCS - SH80UA, WL

Controller P. C. B Ass'y

CR - TH2442

Control circuit fuse

250 VAC, 3 A

Fan (Number … diameter)

in.

(mm)

Turbo (1…17-7/16 (443))

Fan motor

Model

SFG6X - 81A6P

Source

230 - 208 V / 1 phase / 60 Hz

No. of pole … r.p.m. (230 V, High)

rpm

6 … 506

Nominal output

W

60

Coil resistance

BRW - WHT

:

75.1

,

ORG - YEL

:

27.4

(Ambient temperature 68

°

F)

WHT - VLT

:

6.7

,

VLT

- PNK

:

42.7

VLT

- ORG

:

20.6

,

YEL

- BLK

:

58.0

Safety device

Operating temperature

Open

°

F

266

±

14.4

Close

°

F

174.2

±

27

Run capacitor

VAC,

µ

F

440 V , 6

µ

F

Electronic expansion valve

Coil

EKV - MOZS742E

Coil resistance (at 20

°

C)

ORG - GRY

:

46

,

YEL

- GRY

:

46

RED - GRY

:

46

,

BLK

- GRY

:

46

Valve body

HKV - 30D27

Heat exchanger

Coil

Aluminum plate fin / Copper tube

Rows … Fins per inch

2 … 14.9

Face area

ft.

2

(m

2

)

8.20 (0.762)

Panel

Model No.

PNR - XH3642

Auto louver motor

MT8 - 3C

Auto louver motor … Rated

V, W,

rpm

240 VAC , 3 W , 3 rpm

Coil resistance (Ambient temperature 77

°

F)

16.430

±

8 %

DATA SUBJECT TO CHANGE WITHOUT NOTICE

1-2 Major Component Specifications

(A) Indoor Unit

Advertising