Service procedures – Sanyo KH2442 / CH2442 User Manual

Page 197

Advertising
background image

1

2

3

4

Section

SM830082

IV - 41

SM830082

4. Service procedures

Set the outdoor unit R.C. address.
Turn on power supply switch.

Execute auto. address operation with the
remote controller.

Press A. ADD (S1) button (See P87).

or

Execute auto. address operation with the
remote controller.

Press A. ADD (S1) button (See P87).

or

CN4: Open (*)
Set the outdoor unit R.C. address.
Turn on power supply switch.

Go next
R.C. line

Go next
R.C. line

Check according the self-diagnostics function table,
see Sec. 12-8, 9, 10, and if there is a location to correct,
correct it.

Note: Check the indoor side drain water.

Recheck the test items before test operation.

Check the indoor and outdoor unit combination (wiring).

Return the remote controller to normal.

Display the combination number.

Set the remote controller to test operation.

No

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Group control

for multiple outdoor

units?

Central control

for multiple outdoor

units?

Finish all

R.C. line?

Finish all

R.C. line?

Single type?

(One indoor unit and one

remote controller for one

outdoor unit)

No

No

Multiple indoor

units for one outdoor

units?

Turn on power supply for indoor units side
first Then turn on power supply for outdoor
unit side.

No

No

Is operation possible?

2231_M_I

Multiple remote

control?

Turn on RCU address SW
of sub remote control unit

Yes

No

Start

End

Test Run Procedure

1)

One of CN006 of all linked outdoor units shold be short.

2)

In case of using system controller, zone registration is required after finishing Test run.

Regarding the zone registration, please refer to page 74 and 75.

NOTE

Advertising