4. Service procedures

(6) R.C. Address Setting Method

(“0” when shipped from factory)

1

ON

ON side

OFF side

2

0

R.C. address

R.C. address

R.C. address

(S3 2P dip switch, green or blue)

(S2 Rotary switch, Black)

00 auto address

Both OFF

Set to 0

1

ON

10

position

20

position

ON side

: S2

: S3

OFF side

Refrigerant circuit address
(2P DIP switch, green or Blue)

Refrigerant circuit address (black)

Refrigerant circuit address
(factory setting = 0)

Outdoor control PCB

2093_C_I

2

0

A. ADD (S1):
Automatic address setting start button
Used for central control (link system)
and group control (Normally, not used)

CN006 (2P Black)

Outdoor unit R.C. address setting method

In case of group control or central control, set the R.C. address to 1, 2, 3, ... according to the No. of outdoor

units.