Service procedures – Sanyo KH2442 / CH2442 User Manual

Page 172

Advertising
background image

4. Service procedures

1

2

3

4

Section

SM830082

IV - 16

13) Symptom: LCD on the remote controller displays “CHECK P05”. (Negative phase

detection operation warning)

14) Symptom: LCD on the remote controller displays “CHECK E15”.

Yes

No

No

No

Yes

Yes

0345_M_I

Start

Check the power breaker etc.
and repair

No problem

Correct the connection

Replace the outdoor PCB

Is the power supply to the outdoor
unit normal?
(Voltage defective phase?)

Does the outdoor unit operate when
two of the three phases are changed?
(Actuation of negative phase protector)

Is there a contact defect in the
3P connector?

No

Yes

Replace the fuse.

Is the fuse (F1, F2) on the indoor
unit PCB blown?

No

No

No

Yes

Yes

Yes

0646_M_S

Start

Repair the wiring.

Select an indoor unit which matches
with the outdoor capacity.

Check the contact.

Perform the same as “CHECK E04”.

When the group of the units are
installed, is there any mis-cross
between interunit control wiring and
refrigerant tubing?

Are the total capacities of indoor units
to that of outdoor units less than 93%?

Are there no contact failure between
outdoor and indoor units?