4. Service procedures

SM830082

IV - 28

1

2

3

4

Section

5

(H)

Set the indoor unit address (Ref. Fig. IV-11, IV-12)

This function is usable if the auto. address operation is not available.
Indoor unit address can be set one by one by remote controller in such case.

1) In case of group control, branch wiring for group control should be removed

temporarily.

2) In case of remote controllerless system, remote controller should be connected

with the indoor unit temporarily.

(Set the No. of R.C. address)

b

Press the

,

and

buttons at the same time for more than 4 seconds.

c

Set the CODE No. 12 to set the No. of R. C. with the

,

( ) button.

d

Set the No. of R. C. which you want to set with

,

(

) button.

e

Press the

button.

UNIT No., CODE No. 12,

and SET DATA (0002) change from flashing to ON state.

(Set the indoor address)

f

Select the CODE No. 13 to set the indoor unit No. with the

,

( ) button.

g

Set the indoor unit No. which you want to set with the

,

(

) button.

h

Press the

button.

UNIT No., CODE No. 13,

and SET DATA (0004) change from flashing to ON

state.

(Set the group address)

i

Select the CODE No. 14 to set group setting with the

,

( ) button.

j

Set the No. of group setting with the

,

(

) button.

k

Press the

button.

UNIT No., CODE No. 14,

and SET DATA change from flashing to ON state.

l

If you made a mistake, press the

button so that setting returns to the initial state.

m

Press the

button to finish this mode.

The display is disappeared.

n

Confirm the indoor unit address (UNIT No.) with the

button after pressing the

ON / OFF button.

o

In case of group control, be sure to restore the branch wiring to its original wiring. In
case of remote controller–less system, remove the remote controller.

NOTE