background image

4. Service procedures

1

2

3

4

Section

SM830082

IV - 8

(4)

LED Indication on the Outdoor Unit’s P.C.B. Ass’y

If something goes wrong with the outdoor unit, LED lamps on the outdoor P.C.B. Ass’y light
up to show the cause of the trouble, in addition to the Alarm message on the remote
controller.

LED 2 on

P.C. board

Remote

controller

LED 1 on

P.C. board

Possible cause of trouble

Normal

Outdoor unit serial communication signal is abnormal.

Outdoor unit address is duplicated.

Other outdoor units are performing auto address and

detecting refrigerant shortage.

FMo • CM thermal protection is in operation.

Power supply voltage is abnormal.

High voltage SW activates

Negative phase protector activates.

Sensor is abnormal. (Open or short)

Abnormal compressor current value is detected.

Auto address failure

Auto address is in operation.

NOTE

: LED lamps OFF

: LED lamps ON (lights up)

*

: LED lamps ON (blink)

No message

E06, E07, L04

*

No message

P02

P04, P05

*

F04~F09

*

H01, H02

*

*

E15, E16

*

*

“SETTING”
flashes.

Flash at the same time

* REFRIGERANT SHORTAGE

Note particularly that a shortage of refrigerant is only shown by the outdoor P.C.B. Ass’y

LEDs and the Alarm Message does not appear on the Indoor Remote Controller . The
compressor keeps running even when the refrigerant is less, so when you find the LED
indication on the outdoor P.C.B. Ass’y, stop the air conditioner immediately to avoid the
compressor damage.

Fig. IV-2

CAUTION

Flash alternately

Outdoor control PCB

2177_C_I

LED1 (D011)

LED2 (D012)