1. Specifications

1-3 Other Component Specifications

(A) Indoor Unit

MODEL No.

XH2442

Power Transformer

ATR – II224A

Rated

Primary

220 VAC, 60 Hz

Secondary

BRN - BRN : 14 V, 0.45 A, RED - RED : 14 V, 0.3 A

Capacity

Coil resistance

WHT - WHT

:

61.0

,

RED - RED

:

1.37

(Ambient temprature 77

°

F)

BRN - BRN

:

0.97 ,

ORG - ORG

:

3.16

Thermistor cut off temperature

°

F

277

Thermistor (Coil sensor) : TH2, 3

PBC - 41E - S14

Coil resistance

k

14

°

F : 23.7

,

41

°

F : 12.1

23

°

F : 18.8

,

50

°

F :

9.7

32

°

F : 15.0

,

59

°

F :

8.0

Thermistor (Room sensor) : TH1

KTEC - 35 - S6

Coil resistance

k

32

°

F : 16.5

,

104

°

F :

2.7

41

°

F : 12.8

,

113

°

F :

2.2

50

°

F : 10.0

,

122

°

F :

1.8

68

°

F :

6.3

,

131

°

F :

1.5

86

°

F :

4.0

,

Drain pump

PJV - 1428AU

Rated

230 / 208 VAC, 12.5 W

Float switch

FS - 0218 - 102

MAX Rated (Contact rated)

50 W, DC 5V, 0.1 mA

Solenoid control valve or coil

Solenoid control valve

IKV - 24D18

Solenoid coil

DKV - MOZS726E

Synchronized Motor

MT8 - 3C