2-15

Compressor Current Detection Circuit

The Compressor Current Detection Circuit detects the compressor current and,
depending on the current range, can stop the compressor motor so it will not be
damaged by overcurrent.

Overcurrent can be caused by several factors, particularly mechanical seizing of the
compressor or liquid backflow. Either of these conditions can hold the compressor
to run, and thus drawing so much current that the motor can burn out.

Fig. 18

Locked Comp. Cut-off Range

Overload Protection Range

Normal Operation Range

Comp. Amps.(A)

Is 1.17

Is 1.4

Is

Rated Current
value

+

+

0447_M_S

Outdoor Model

Rated Current Value

Overload Protection

Locked Compressor Cut-off

ls (A)

ls x 1.17 (A)

Is x 1.4 (A)

CH2442

17.1

20.0

23.9

CH3642

27.5

32.2

38.5

CH4242

34.7

40.6

48.6

Chart Summary and Explanations

Overload Protection

When the detected current is 1.17 – 1.4 times greater than the rated current value (Is) and continues
for 30 seconds, both compressor and outdoor fan stop (Thermostat OFF).

After 3-minute pause, if the air conditioner is ready for Thermostat ON, it starts again. However, if the
condition mentioned above repeats twice within 30 minutes, the remote controller displays the alarm
message H01, compressor overload.

Locked Compressor Cut-off

When the detected current is 1.4 times greater than the rated current value (ls) and continues for 2
seconds
, both compressor and outdoor fan stop (Thermostat OFF).

After 3-minute pause, if the air conditioner is ready for Thermostat ON, it starts again. However, if the
condition mentioned above repeats twice, the remote controller displays the alarm message H02,
compressor locked.

Failure of Compressor Current Detection

When the Compressor Current Detection Circuit fails to detect the compressor current within 2
seconds after compressor starts
, both compressor and outdoor fan stop (Thermostat OFF).

After 3-minute pause, if the air conditioner is ready for Thermostat ON, it starts again. However, when
the circuit fails to detect the current twice in a row, the remote controller displays alarm message H03,
Failure of compressor Current Detection.