7 overload protection (heating), Processes and functions – Sanyo KH2442 / CH2442 User Manual

Page 129

Advertising
background image

II - 9

SM830082

1

2

3

4

Section

5

2. Processes and functions

Fig. 10

2-7

Overload Protection (Heating)

This function prevents the air conditioner from overloading.

Chart Explanations and notes

This chart shows how the outdoor fan speed and the electronic refrigerant control valve
react to coil temperature to keep the indoor heat exchanger coil from overloading.

When sensor E2 rises above 140°F the electronic refrigerant control valve opens at 50
steps/30 seconds until E2 falls below 138°F.

Sensor E2 is located in the middle of the indoor unit heat exchange unit.

When sensor E2 rises above 144°F, the control circuit stops the outdoor fan motor till the
temp. drops to 131°F

Fuzzy control controls the electronic refrigerant control valve.

(

°

F)

ELECTRONIC REF.
CONTROL VALVE

INDOOR UNIT COIL
TEMP. (E2)

147

144

140

138

131

127

OUTDOOR FM

START UP

COMPENSATION

OFF

OPEN

H OR M

H OR M

H

L

1927_THS_I

FUZZY CONTROL

FUZZY CONTROL

OVERLOAD
PROTECTION

OVERLOAD PROTECTION

OPEN