4. Service procedures

11) Symptoms: LCD on the remote controller displays “CHECK P03”.

(Alarm for unusual discharge temp. of compressor)

12) Symptom: LCD on the remote controller displays “CHECK P04”. (High-pressure switch

activation warning)

0343_M_I

Start

Unusual discharge gas temperature

• Refrigerant shortage
• Clogged refrigerant circuit
• Electronic refrigerant control

valve defect (indoor unit)

No

Yes

No

Yes

0344_M_I

Start

Are there connection defects in
the wiring?

High-pressure switch defect

Repair the wiring.

The system does not operate again.

High-pressure switch activation

(Both cooling and heating)
• Electronic refrigerant control valve

defect

• Refrigerant over-charged

(Cooling)

• Outdoor unit, heat exchanger dirty,

clogged

• Outdoor unit air short
• Outdoor fan stopped

(Heating)

• Outdoor unit air short
• Indoor unit, heat exchanger dirty,

clogged

• Large pipe side service valve

closed

• Indoor fan stop
• Air filter clogged